Si34-704 Field Setting
Test Operation 149
3.1.5 Applicable Range of Field Setting
1
Static pressure selection
3.1.6 Detailed Explanation of Setting Modes
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
Ultra-Long-Life Filter Sign Setting
When a Ultra-long-life filter is installed, the filter sign timer setting must be changed.
Setting Table
Ceiling mounted cassette
type
Slim
Ceiling
mounted
duct
type
Ceiling
mounted
built-in
type
Ceiling
mounted
duct
type
Ceiling
suspende
d type
Wall
mounted
type
Floor
standing
type
Conceale
d Floor
standing
type
New
Ceiling
suspende
d cassette
type
Outdoor
air
processing
unit
Multi
flow
Double
flow
Corner
type
FXFQ FXCQ FXKQ FXDQ FXSQ FXMQ FXHQ FXAQ FXLQ FXNQ FXUQ
FXMQ-
MF
Filter sign
{{{{{{{{{{{{
Ultra long life filter
sign
{{
—————————
Remote controller
thermostat sensor
{{{{{{{{{{{
Set fan speed when
thermostat OFF
{{{{{{{{{{{
Air flow adjustment
Ceiling height
{
———
{
———
{
Air flow direction
{
————————
{
Air flow direction
adjustment
(Down flow operation)
——
{
—————————
Air flow direction
adjustment range
{{{
—————————
Field set fan speed
selection
{
——
{
1—
{
—————
Discharge air temp.
(Cooling)
——————
{
Discharge air temp.
(Heating)
——————
{
Filter Specs.
Setting
Standard Long Life Ultra Long Life Filter
Contamination Light 200 hrs. 2,500 hrs. 10,000 hrs.
Contamination Heavy 100 hrs. 1,250 hrs. 5,000 hrs.
Mode No. Setting Switch No. Setting Position No. Setting
10 (20) 1
01 Long-Life Filter
02 Ultra-Long-Life Filter (1)
03