Daikin FXDQ20PVET [217/394] Troubleshooting

Daikin RXQ50PHY1 [217/394] Troubleshooting
Troubleshooting by Indication on the Remote Controller Si34-704
206 Troubleshooting
Troubleshooting
NO
Electronic
expansion valve is
connected to X7A of
indoor unit
PCB.
Coil
check (1) of
electronic expansion valve
drive indicates
normal.
NO
NO
YES
Relay
cables short circuit or
disconnected.
YES
Shut the power supply off after
connection and then restart.
Replace coil of electronic
expansion valve.
Replace relay cables.
When restarting the operation after
shutting the power supply off does
not work, replace indoor unit PCB.
NO
Replace electronic expansion
valve main body.
When power is supplied.
YES
YES
1: How to check the coil of electronic expansion valve drive
Remove the connector for electronic expansion valve (X7A) from PCB. Measure the resistance value
between pins and check the continuity to judge the condition.
1) White
2) Yellow
3) Orange
4) Blue
6) Brown
5) Red
The normal products will show the following conditions:
No continuity between (1) and (2)
Resistance value between (1) and (3) is approx. 300
Resistance value between (1) and (5) is approx. 150
Resistance value between (2) and (4) is approx. 300
Resistance value between (2) and (6) is approx. 150
White (1)
Red (5)
Orange (3)
φ1
φ3
Yellow
(2)
Brown
(6)
Blue
(4)
φ2 φ4
M
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.