Daikin FXDQ20PVET [238/394] Outdoor unit malfunction of moving part of electronic expansion valve y1e y2e

Daikin RXQ36PHY1 [238/394] Outdoor unit malfunction of moving part of electronic expansion valve y1e y2e
Si34-704 Troubleshooting by Indication on the Remote Controller
Troubleshooting 227
3.20
E9
Outdoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y1E, Y2E)
Remote
Controller
Display
E9
Applicable
Models
RXQ5P~54P
Method of
Malfunction
Detection
Check disconnection of connector
To be detected based on continuity existence of coil of electronic expansion valve (Y1E)
Malfunction
Decision
Conditions
No current is detected in the common (COM [+]) when power supply is ON.
Supposed
Causes
Disconnection of connectors for electronic expansion valve (Y1E)
Defect of moving part of electronic expansion valve
Defect of outdoor unit main PC board (A1P)