Daikin FXDQ20PVET [263/394] Outdoor unit momentary overcurrent of inverter compressor

Daikin FXDQ32PVET [263/394] Outdoor unit momentary overcurrent of inverter compressor
Troubleshooting by Indication on the Remote Controller Si34-704
252 Troubleshooting
3.36
L8
Outdoor Unit: Momentary Overcurrent of Inverter
Compressor
Remote
Controller
Display
L8
Applicable
Models
RXQ5P~54P
Method of
Malfunction
Detection
Malfunction is detected by current flowing in the power transistor.
Malfunction
Decision
Conditions
When overload in the compressor is detected. (Inverter secondary current 16.1A)
16.1A and over continues for 260 seconds.
Supposed
Causes
Compressor overload
Compressor coil disconnected
Defect of inverter PC board
Faulty compressor