Si34-704 Troubleshooting by Remote Controller
Troubleshooting 191
8: ON 7: OFF 9: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No. Malfunction contents Page
Referred
Indoor Unit A0 999Error of external protection device 198
A1 999PC board defect, E
2
PROM defect 199
A3 999Malfunction of drain level control system (S1L) 200
A6 999Fan motor (M1F) lock, overload 202
A7 879Malfunction of swing flap motor (M1S) 203
A9 999Malfunction of moving part of electronic expansion
valve / Dust clogging
205
AF 879Drain level about limit 209
AH 879Malfunction of air filter maintenance
AJ 999Malfunction of capacity setting 210
C4 999Malfunction of thermistor (R2T) for heat exchange
(loose connection, disconnection, short circuit, failure)
211
C5 999Malfunction of thermistor (R3T) for gas pipes (loose
connection, disconnection, short circuit, failure)
212
C9 999Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
213
CA 999Malfunction of discharge air thermistor (R4T) 214
CJ 888Malfunction of thermostat sensor in remote controller 215
Outdoor Unit E1 999PC board defect 216
E3 999Actuation of high pressure switch 217
E4 999Actuation of low pressure sensor 219
E5 999Compressor motor lock 221
E6 999Standard compressor lock or over current 223
E7 999Malfunction of outdoor unit fan motor 224
E9 999Malfunction of moving part of electronic expansion
valve (Y1E, Y2E)
227
F3 999Abnormal discharge pipe temperature 229
F6 999Refrigerant overcharged 231
H7 999Abnormal outdoor fan motor signal 232
H9 999Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
234
J2 999Current sensor malfunction 235
J3 999Malfunction of discharge pipe thermistor (R3, R31,
32T) (loose connection, disconnection, short circuit,
failure)
236
J5 999Malfunction of thermistor (R2T), (R7T) for suction
pipe (loose connection, disconnection, short circuit,
failure)
238
J6 999Malfunction of thermistor (R4T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
239
J7 999Malfunction of receiver outlet liquid pipe thermistor (R6T) 240
J9 999Malfunction of subcooling heat exchanger gas pipe
thermistor (R5T)
242
JA 999Malfunction of high pressure sensor 243
JC 999Malfunction of low pressure sensor 245
L1 999Malfunction of inverter PC board 247
L4 999Malfunction of inverter radiating fin temperature rise 248
L5 999DC output overcurrent of inverter compressor 250
L8 999Inverter current abnormal 252
L9 999Inverter start up error 254