ESIE09-08B Field Setting
Test Operation 95
[6] Option setup
[6-00] Domestic hot water tank option
If the domestic hot water tank is installed, its operation must be enabled by field setting.
Default [6-00] = 0 which means no tank is installed. Set [6-00] to 1 if the optional domestic
hot water tank is installed.
Note
: When enabling the domestic hot water tank option be aware that the advised default settings
b
ec
ome active:
[1-00] = 1 = automatic night storage
[4-00] = 1 = disinfection function
[6-01] External ro
om thermo
stat option
If the optional external room thermostat is installed, its operation must be enabled by field
setting. Default [6-01] = 0, which means no external room thermostat is installed. Set [6-01]
to 1 if the optional external room thermostat is installed.
The external room thermostat only gives an ON/OFF signal to the heat pump based on the
room temperature. Because it does not give continuous feedback information to the heat
pump,
it is supplementary to the remote controller room thermostat function. To have a good
control of the system and avoiding frequent ON/OFF it is advised to use the automatic
weather dependent set point operation.
Note : By using an external room thermostat, the smart logic of the standard remote controller is
o
v
erruled.
[6-02] Heater kit
Once installed, you can activate the heater kit by changing field setting [6-02]=1.
From that moment on, the heat pump system will take the heater kit into account whilst
deciding operation. When
the heater
is actually operating, the heater symbol is shown on the
remote controller. There is no step 1-2 indication.
For more information see “Part 9 - External Backup Heater Kit” on page 255.
[6-03] Solar support
For more information refer to the EKHWP installation manual.
[6-04] Benefit kWh rate power supply mod
e
If benef
it kWh rate power supply is used, the mode must be selected. Default [6-04] = 0
which means no benefit kWh rat
e power supply is used.
Set [6-04] to 1 to use benefit kWh rate power supply mode 1 (normally closed contact which
will open when the power supply is interrupted), or se
t [6-04] to 2 to use benefit kWh rate
power sup
ply mode 2 (normally opened contact which will close when the power supply is
interrupted).
First
code
Second
code Setting name
Default
value Range Step Unit
6 Option setup
00 Domestic hot water tank installed 0
(OFF)
0/1
01 Op
tional room thermostat installed 0
(OFF)
0/1
04 Benefit kWh pow
er supply mode 0 0/2 1