ESIE09-08B Field Setting
Test Operation 83
C Leaving water temperature limits
00 Set point: leaving water maximum
temper
ature
80 37~80 1 °C
01 Set point: leaving water minimum
temper
ature
25 25~37 1 °C
02 Not applicable. Do not change the default
valu
e.
20 18~22 1 °C
03 Not applicable. Do not change the default
valu
e.
5 5~18 1 °C
D Domestic water heating retention times
00 Set point: minimum time for domestic water
heating
10 5~
20 1
01 Set point: maximum time for domestic water
heating
30 10~60 5
02 Set point: interval min
imum stop time of
domestic water hea
ting
15 5~30 5
E Service mode
00 Vacuum mode 0 0/1
01 Not applicable. Do not change the default
valu
e.
0
(OFF)
0/1
02 Not applicable. Do not change the default
valu
e.
0
(OFF)
0/1
03 Not applicable. Do not change the default
valu
e.
1 0~2 1
04 Pump only operation 0 0~2 1
First
code
Second
code Setting name
Installer setting at variance with
default value
Default
value Range Step UnitDate Value Date Value