ESIE09-08B Troubleshooting by Indication on the Remote Controller
Troubleshooting 201
Troubleshooting
: Refer to information on P211.
Caution
Be sure to turn off power switch before connect or disconnect
connector, or parts damage may be occured.
(V3187)
Is
indoor -
outdoor unit
transmission wiring
normal?
Repair the broken wires, and
then restart operation.
Replace the fuse.
Fix the indoor/outdoor unit
transmission wiring.
Push and hold the RESET
button on the outdoor unit PC
board for 5 seconds.
Replace the outdoor unit PC
board (A1P).
YES
YES
NO
YES
Replace the indoor unit PC
board (A1P).
Fix the indoor/outdoor unit
transmission wiring.
YES
NO
NO
YES
Has
the indoor
or outdoor unit
PC board been
replaced, or has the indoor -
outdoor unit transmission
wiring been
modified?
Indoor unit
remote controller
displays “U4”
NO
Outdoor unit
PC board microcomputer
monitor (HAP) blinks.
NO
NO
NO
Operation
ready lamp (H2P) is
blinking.
Lamp does not
go off for 12 minutes or
more.
Is
indoor -
outdoor unit
transmission wiring
normal?
YES
The fuse F3U on
the outdoor unit's PC board is
burnt.
Replace outdoor unit PC
board (A1P).
YES
YES
Has
either the fuse
F4U on the outdoor
unit PC board (A1P) or the
fuse F1U on the inverter
PC board (A2P)
blown out?
NO
Are there
any broken wires in
the connectors of the inverter
PC board (A1P) and the
control PC board
(A2P)?
Reset the power supply.
YES
YES
YES
Supply 220~240 V.
NO
YES
NO
NO
NO
The
voltage between
terminals L3 and N of the
outdoor unit PC board is
220~240 V.
Is
resistance
between pins in excess of
judgment criteria?
Replace the fuse F4U and
the inverter PC board (A2P).
Replace the fan motor.
Replace the inverter PC
board (A2P).
Replace the fuse F4U.
Check No.3