õUNGHEINRICH Event Messages
03.15168
G
_7031
Undefined
Inching speed monitoring:
Travel
The truck function has requested a truck deceleration
to2.5 km/h. However the required deceleration to crawl
speed was not introduced within 1 second.
-Check the inching speed setting against the
data sheet values;
-Check the brake ramp settings;
Undefined
Inching speed monitoring:
Main Lift
The truck function has requested a reduction of the main
lift speed to crawl speed. However the reduction of the
main lift speed was not introduced within 1 second.
-Check the inching speed setting against the
data sheet values;
-Check the brake ramp settings;
_7032Undefined
Inching speed monitoring:
Aux. lift
The truck function has requested a reduction of the
aux.lift speed to crawl speed. However the reduction of
the aux. lift speed was not introduced within 1 second.
-Check the inching speed setting against the
data sheet values;
-Check the brake ramp settings;
_7033Undefined
Inching speed monitoring:
Sideshift
The truck function has requested a reduction of the
sideshift speed to crawl speed. However the reduction of
the sideshift speed was not introduced within 1 second.
-Check the inching speed setting against the
data sheet values;
-Check the brake ramp settings;
_7034Undefined
Inching speed monitoring:
Rotate
The truck function has requested a reduction of
therotary speed to crawl speed. However the reduction
ofthe rotary speed was not introduced within 1 second.
-Check the inching speed setting against
thedata sheet values;
-Check the brake ramp settings;
_7041
Undefined
Maximum speed monitoring:
Travel
The travel speed has been exceeded by more than
0.5km/h.
-Check the maximum speed setting against
thedata sheet values;
-Check the brake ramp settings;
Undefined
Maximum speed monitoring:
Main Lift
The main lift speed has been exceeded by more
than0.025 m/sec.
-Check the maximum speed setting against
thedata sheet values;
-Check the brake ramp settings;
_7042Undefined
Maximum speed monitoring:
Aux. lift
The aux. lift speed has been exceeded by more
than0.025 m/sec.
-Check the maximum speed setting against
thedata sheet values;
-Check the brake ramp settings;
_7043Undefined
Maximum speed monitoring:
Sideshift
The sideshift speed has been exceeded by more
than0.025 m/sec.
-Check the maximum speed setting against
thedata sheet values;
-Check the brake ramp settings;
F E XX SOperational
Status
DescriptionCause / Triggering EventAction