VTS Ventus VVS650 [26/55] Power supply and control circuits

VTS Ventus VVS650 [26/55] Power supply and control circuits
Controls
50
POWER SUPPLY AND CONTROL CIRCUITS
» The mains component of the controls is the control box – with microprocessor controller installed inside.
The control box is usually mounted on side wall of the AHU or in units direct vicinity.
» Control box is equipped with controller, power protection circuits, terminal block enabling connecting
of all control elements.
» Electric protection of fans, rotary heat wheel drive, control elements and heater pump are installed inside
the control box.
» Control of fan-sets (variable frequency drives in case of AC motors of specialized drives for EC ones)
is realized by means of digital communication based on ModBUS protocol. Fan control elements are set
with individual address enabling them to be properly identied in the control system.
» Communication with static pressure and CO2 transducers also realized by ModBUS protocol.
» For other control elements, digital or analogue signals are used.
PREVENTIVE FUNCTIONS
» Constant lter contamination status control:
Constant monitoring of lter pressure drop by means of static pressure transducers,
Evaluation of lter contamination status for vs actual airow rate.
» Fans shutting-down delay – fans run out for systems with electric heater
» Water heater pre-heating before funs start up.
» Periodical heater pump engaging in summer – to prevent against limescale accumulation
» Opening of water heater regulation valve before engaging the fans.
TIME SCHEDULE FUNCTIONS
» Weekly schedule operational modes programming (HMI Advanced i Basic).
» Clear visualization of schedule settings by means of web-browser (computers and mobile devices).

Содержание

Скачать