Design Features (cont'd)
Controls
The SWS units are supplied with a microprocessor based electronic
control and management system ensuring the following functions :
Management of liquid / pump down solenoid valves :
- Compressor starts when solenoid valve is energized.
- Pump down takes place when solenoid valve is de-energized.
Management of compressor operation :
- Start-up / Stop.
- Management of delays at start-up.
- Rotation of compressors.
Chilled/hot water temperature control on evaporator
water return or leaving :
- Control on return water : proportional type (RWT P) or
proportional integral type (RWT P+I) with integration time to be
parametrized.
- Control on leaving water (LWT).
Standard control : RWT P.
Evaporator anti-freeze protection.
Management of high and low pressure alarms.
Remote control management :
- Unit start-up and stop.
- Alarm signalling.
Programming of 4 hour periods with 4 different set
points.
Alarm records.
Counting of compressor and pump (if present) operation
hours.
Double set points.
The electronic controller provides for a clear signalling, on the LCD,
of any unit control parameters, such as :
- Display of the circuit 1 and circuit 2 discharge pressure.
- Display of the circuit 1 and circuit 2 suction pressure.
- Display of the return water temperature.
- Display of the leaving water temperature.
- Display of the various alarms and operation states :
Inlet water temperature.
Outlet water temperature.
High / low pressure.
Evaporator anti-freeze.
Lack of water.
Phase sequence monitoring.
Compressor thermal protection.
Remote unit OFF.
- Remote ON/OFF contact.
- Contacts for the forced unloading of compressors or for the
second set point.
- Contacts signalling that the compressors are running.
- Contact signalling that the unit is switched on.
- Contact signalling that the unit is alarmed.
Factory-installed options
Condensers for well water.
Suction valve.
Liquid injection circuit.
Electronic expansion valves.
LN (Low Noise) kit (supplied loose or fitted).
Compressor oil level sensor kit.
Field-installed accessories
Gauges.
Spring anti-vibration mounts.
Remote keyboard.
RS485 ModBus serial interface (BMS).
Chiller NET-Control :
Master/slaves communication capability to monitor, from a
"master" unit, up to 4 units on a common hydraulic circuit.
Chiller Black Box :
Electronic board memorizing machine information intended for
maintenance works :
- Last memorized alarms (date and type).
- Entering and leaving water temperature report.
- Suction and discharge pressure report.
GSM modem :
For information communication and transfer by SMS (SIM card
not supplied).