Fluke 345 [23/80] Power quality clamp meter

Fluke 345 [23/80] Power quality clamp meter
Power Quality Clamp Meter
Specifications
9
Inrush Current Function
Ranges ............................................................... 40, 400 and 2000 A
Resolution........................................................... 10 mA in 40 A range
100 mA in 400 A range
1 A in 2000 A range
Accuracy
I > 10 A .......................................................... ± 5 % rdg ± 1 pixel
I < 10 A ........................................................... ± 0.5 A
All measurements DC and 15 Hz to 1 kHz
Maximum overload ............................................ 10,000 A or rms x frequency <
400,000.
Amps rms is a true rms measurement (AC + DC)
Capture time ....................................................... 1, 3, 10, 30, 100 and 300 s
Sampling rate...................................................... 15.625 kHz
Digital Output
USB Interface to a PC
Power Log software for download, analysis and reporting
345 Upgrade Utility for installing a new firmware version
Logging Memory
Logging Areas..................................................... Three areas that can be used
individually or combined into one large
area.
Averaging periods............................................... 1 s, 2 s, 5 s, 10 s, 30 s, 1 min, 5 min,
10 min, 15 min, and custom