Delta Electronics VFD037CB43A-20 [117/363] 3 high starting torque

Delta Electronics VFD022CB43A-20 [117/363] 3 high starting torque
Chapter 11 Description of Parameter Settings|C200 Series
11-18
(3) High starting torque
60.0
01-00
01-01
01-02
01-03
01-05
01-04
01-06
01-07
01-08
60.0
220.0
3.00
23.0
1.50
18.0
50.0
01-00
01-01
01-02
01-03
01-05
01-04
01-06
01-07
01-08
50.0
220.0
2.20
23.0
1.30
14.0
Motor spec. 60Hz
Motor spec. 50Hz
Pr. Setting
Pr.
Setting
V
F
220
18
1.5
60.0
23
3
V
F
220
14
1.3
50.0
23
2.2
Start-Up Frequency
Factory Setting: 0.50
Settings 0.0~600.00Hz
When start frequency is higher than the min. output frequency, drives’ output will be from start
frequency to the setting frequency. Please refer to the following diagram for details.
Fcmd=frequency command,
Fstart=start frequency (Pr.01-09),
fstart=actual start frequency of drive,
Fmin=4th output frequency setting (Pr.01-07/Pr.01-41),
Flow=output frequency lower limit (Pr.01-11)
Fcmd>Fmin
Fstart>Fmin
NO
YES
YES
fstart=Fstart
NO
fstart=Fmin
Flow=0
Flow=0
YES
H=Fcmd
YES
H=Fcmd
NO
Fcmd>Flow
YES
Fcmd>Fmin
YES
H=Fcmd
NO
NO
Fcmd<Fmin
NO
H=Flow
YES
NO
Fcmd
Fmin
Fstart
Fcmd
Fmin
Fstart
Fcmd1>Flow &
Fcmd1>Fmin
Fmin
Flow
Fcmd2>Flow &
Fcmd2<Fmin
Flow>Fcmd1
>Fmin
Fmin
Flow
Fmin>Fcmd2
60Hz
60Hz
Hz
Time
Hz
Time
Time
Time
Hz
Hz
Fcmd1
Fcmd2
H=Flow
Fcmd1
Fcmd2
H=Fc md1
by Pr.01-34
by
Pr.01-34
by
Pr.01-34
by Pr.01-34
by Pr.01-34
operation after
start-up