Daikin FXSQ80P7VEB [100/370] Compressor control

Daikin FXHQ63MAV7 [100/370] Compressor control
Normal Operation SiBE311209
91 Function
6.2 Compressor Control
6.2.1 Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
[Heating operation]
[Heating operation at low outdoor air temperature]
<Outdoor unit>
This function is used to conduct the same control as that for "Heating operation"
aforementioned.
<Function unit>
This function is used to control the compressor capacity so that the ratio (Ph) of the high-stage-
side compression ratio to the low-stage-side compression ratio will come to the target value.
Pc: Value detected by the high pressure sensor of the function unit (MPa)
Pm: Value detected by the high pressure sensor of the outdoor unit (MPa)
Pe: Value detected by the low pressure sensor of the outdoor unit (MPa)
k
Target value of Ph: PhS = 0.5 to 2.0
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te: Low pressure equivalent saturation
temperature (°C)
Te set value (Make this setting while in Setting
mode 2.)
TeS: Target Te value
(Varies depending on Te setting, operating
frequency, etc.)
On multi-outdoor-unit systems, this control is made
according to values of the first-priority unit, which is
detected with the pressure sensor.
Te setting (°C)
LM (Normal)
(factory
setting)
H
3 6 7 8 9 10 11
Controls compressor capacity to adjust Tc to
achieve target value (TcS).
Tc: High pressure equivalent saturation
temperature (°C)
Te set value (Make this setting while in Setting
mode 2.)
TcS: Target Tc value
(Varies depending on Tc setting, operating
frequency, etc.)
On multi-outdoor-unit systems, this control is made
according to values of the first-priority unit, which is
detected with the pressure sensor.
Tc setting (°C)
LM (Normal)
(factory
setting)
H
43 46 48
k
Ph =
High-stage-side compression ratio
=
Pc/Pm
Low-stage-side compression ratio Pm/Pe
Pressure
Enthalpy
Electronic expansion
valve (1)
Gas & liquid separator
Electronic expansion
valve (2)
Function unit
Outdoor unit
High
pressure
(Pc)
Intermediate
pressure (Pm)
Low
pressure
(Pe)