Daikin FXSQ80P7VEB [250/370] Electronic expansion valve coil y1e y3e abnormality

Daikin FXZQ25MVES [250/370] Electronic expansion valve coil y1e y3e abnormality
Troubleshooting by Indication on the Remote Controller SiBE311209
241 Service Diagnosis
4.20 Electronic Expansion Valve Coil (Y1E~Y3E) Abnormality
Remote
Controller
Display
E9
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Function Unit: BTSQ20PY1
Method of Error
Detection
Check continuity of electronic expansion valve
Error Decision
Conditions
No current is detected in the common (COM [+]) when power supply is ON.
Supposed
Causes
Disconnection of connectors for electronic expansion valve (Y1E)
Defective electronic expansion valve coil
Defective outdoor unit main PCB (A1P)