Daikin FXSQ80P7VEB [158/370] Simplified remote controller

Daikin FXSQ50PVE [158/370] Simplified remote controller
Field Setting SiBE311209
149 Test Operation
3.1.3 Simplified Remote Controller
BRC2A51
BRC2C51
1. Remove the upper part of remote controller.
2. When in the normal mode, press the [BS6] BUTTON () (field set), and the FIELD
SETTING MODE is entered.
3. Select the desired MODE No. with the [BS2] BUTTON () (temperature setting
V
) and the
[BS3] BUTTON () (temperature setting
W
).
4. During group control, when setting by each indoor unit (mode No. 20, 22, and 23 have been
selected), press the [BS8] () BUTTON (unit No.) and select the INDOOR UNIT NO. to be
set. (This operation is unnecessary when setting by group.)
5. Press the [BS9] BUTTON () (set A) and select FIRST CODE NO.
6. Press the [BS10] BUTTON () (set B) and select SECOND CODE NO.
7. Press the [BS7] BUTTON () (set/cancel) once and the present settings are SET.
8. Press the [BS6] BUTTON () (field setting) to return to the NORMAL MODE.
9. (Example) If during group setting and the time to clean air filter is set to FILTER
CONTAMINATION - HEAVY, SET MODE NO. to “10”, FIRST CODE NO. to “0”, and
SECOND CODE NO. to “02”.
MODE NO.
UNIT NO.
FIRST
CODE NO.
SECOND
CODE NO.
(7) (4) (5) (6)(2)(8)
(3)
(3)

Содержание

Скачать