Daikin FXSQ80P7VEB [131/370] When the float switch is tripped and af is displayed on the remote controller

Daikin FXHQ100MAVS [131/370] When the float switch is tripped and af is displayed on the remote controller
SiBE311209 Outline of Control (Indoor Unit)
Function 122
9.3.3 When the Float Switch is Tripped and “AF” is Displayed on the
Remote Controller:
4. (Error residual):
If the float switch is tripped 5 times in succession, a drain error is determined to have occurred.
AF
” is then displayed as operation continues.
5. (Error residual):
The remote controller will display "
A3
" and the air conditioner will come to an abnormal stop if
the float switch is OFF for more than 5 minutes in the case of 4.
Remote
controller display
Drain pump
OFF
ON
"
AF
" display (running)
Float switch
OFF
ON
1 : 5 min.
1st time 2nd time 3rd time 4th time 5th time
Enters error treatment if the
float switch is not reset within
5 minutes.
Remote controller "
A3
"
blinking abnormal stop
1
111111
5 sec.
54
ON
OFF

Содержание