Troubleshooting by Indication on the Remote Controller SiBE311209
293 Service Diagnosis
4.52 Transmission Error between Indoor Units and Outdoor
Units in the Same System
Remote
Controller
Display
U9
Applicable
Models
All indoor unit models
Outdoor Unit: RTSQ8~16PAY1
Method of Error
Detection
Detect error signal for the other indoor units within the circuit by outdoor unit PCB.
Error Decision
Conditions
When the error decision is made on any other indoor unit within the system concerned
Supposed
Causes
Transmission error within or outside of other system
Electronic expansion valve abnormality in indoor unit of other system
Defective PCB of indoor unit in other system
Improper connection of transmission wiring between indoor and outdoor unit
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Continue the operation.
YES
Turn ON all indoor units.
NO
NO
YES
All the units are
indicating “
U9
”.
"
U9
" has been
displayed for 2
minutes or more.
Re-diagnose by display after
passage of 2 minutes or more.
The outdoor unit PCB indicated by
the error code
U9
is normal.
Check for the indoor unit of other
system, and then conduct
troubleshooting by diagnosis
according to the Error Code
Flowchart.