Daikin FXSQ80P7VEB [230/370] Troubleshooting

Daikin FXSQ32PVE4 [230/370] Troubleshooting
Troubleshooting by Indication on the Remote Controller SiBE311209
221 Service Diagnosis
Troubleshooting
Note:
1:How to check the electronic expansion valve coil
Remove the connector for electronic expansion valve (X7A) from PCB. Measure the resistance value between
pins and check the continuity to judge the condition.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Replace the electronic expansion
valve main body.
NO
NO
NO
YES
YES
YES
Shut the power supply OFF after
connection and then restart.
Replace the electronic expansion
valve coil.
Replace the relay cables.
When restarting the operation after
shutting the power supply OFF
does not work, replace the indoor
unit PCB.
When power is supplied.
Electronic
expansion valve is
connected to X7A of
indoor unit PCB.
Check (1) of
electronic
expansion valve
coil indicates
normal.
Relay cables short
circuit or
disconnected.
White (1)
Red (5)
Orange (3)
φ1
φ3
M
φ2 φ4
Yellow
(2)
Brown
(6)
Blue
(4)
1) White
2) Yellow
3) Orange
4) Blue
5) Red
6) Brown
The normal products will show the following conditions:
(1) No continuity between (1) and (2)
(2) Resistance value between (1) and (3) is approx. 300
(3) Resistance value between (1) and (5) is approx. 150
(4) Resistance value between (2) and (4) is approx. 300
(5) Resistance value between (2) and (6) is approx. 150