Daikin FXSQ80P7VEB [328/370] 1 turn off the power supply 2 measure the resistance between vcc and each phase of u v w and gnd and each phase at the motor side connectors 5 core wire to check that the values are balanced within the range of 20 while connector or relay connector is disconnected furthermore to use a multiple meter for measurement connect the probe of negative pole to vcc and that of positive pole to gnd

Daikin FXZQ40MVE4 [328/370] 1 turn off the power supply 2 measure the resistance between vcc and each phase of u v w and gnd and each phase at the motor side connectors 5 core wire to check that the values are balanced within the range of 20 while connector or relay connector is disconnected furthermore to use a multiple meter for measurement connect the probe of negative pole to vcc and that of positive pole to gnd
Troubleshooting by Indication on the Remote Controller SiBE311209
319 Service Diagnosis
Check on Connector of Fan Motor (Power Supply Cable)
(1) Turn OFF the power supply.
Measure the resistance between phases of U, V, W at the motor side connectors (3-core
wire) to check that the values are balanced and there is no short circuit, while connector or
relay connector is disconnected.
(1) Turn OFF the power supply.
(2) Measure the resistance between Vcc and each phase of U, V, W, and GND and each phase
at the motor side connectors (5-core wire) to check that the values are balanced within the
range of ± 20 %, while connector or relay connector is disconnected.
Furthermore, to use a multiple meter for measurement, connect the probe of negative pole
to Vcc and that of positive pole to GND.
CHECK 16
Measure the resistance
values between phases
U, V, W.
Red
White
Black
W
V
U
CHECK 17
Measure the resistance
values between Vcc
and U, V, W, and GND
and U, V, W.
GND
Vcc
W
V
U
5 Gray
4 Pink
3 Orange
2 Blue
1 Yellow