SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 290
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Confirmation of
error 3
Diagnosis Flow 6
Confirmation of
error 4
Are manual address settings (of the
slave units 1 and 2) correct in order to
connect the AIRNET?
NO
YES
Correct the manual address
settings.
(For detail, refer to information in
the "AIRNET Installation Manual".)
Correct the transmission wires of
the outdoor multi and then reset
the power supply.
Replace the outdoor unit main PCB
(A1P).
Check the connection status of one of
the connecting wires of Outdoor Multi.
Check if the wiring is broken or
disconnected.
YES
NO
Confirmation of
error 3
Diagnosis Flow 7
Confirmation of
error 4
In the connection status of
the outdoor multi, check if
more than 4 outdoor units
are connected.
YES
NO
Correct the transmission wires of
the outdoor multi and then reset
the power supply.
Replace the outdoor unit main PCB
(A1P).
Confirmation of
error 3
Diagnosis Flow 8
Confirmation of
error 4
Check the connection status of the
connecting wires of outdoor multi.
Check if the wiring has any connection
error or broken, or is about to be
disconnected.
YES
NO
Correct the transmission wires of
the outdoor multi and then reset
the power supply.
Replace the outdoor unit main PCB
(A1P).