Daikin FXSQ80P7VEB [284/370] Note 1 list of compressor inverter pcbs

Daikin FXZQ50M9V1B [284/370] Note 1 list of compressor inverter pcbs
Troubleshooting by Indication on the Remote Controller SiBE311209
275 Service Diagnosis
Troubleshooting
Note: 1. List of Compressor Inverter PCBs
2. List of fan Inverter PCBs
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
Make correct setting of
DIP switch.
(For setting procedure,
refer to information on
P.164.)
Was the PCB
(A1P) replaced
with a spare
PCB?
NO
Is the model
setting of the
spare PCB
correct?
Is the type of the
compressor inverter
PCB correct? (1)
Is the type of the fan
inverter PCB
correct? (2)
Does the
preparation
indication lamp on
the outdoor unit
main PCB turn
OFF?
Replace it with the
correct compressor
inverter PCB.
Replace it with the
correct fan inverter
PCB.
Rectify the connection
wiring.
Replace the outdoor
unit PCB.
YES
YES
NO
YES
NO
YES
NO
YES
Model Applicable Models
PC0509-1
RTSQ8 ~ 16PA
BTSQ20P
Model Applicable Models
PC0511-1 RTSQ8 · 10 · 12PA
PC0511-3
PC0511-4
RTSQ14PA
PC0511-1
PC0511-12
RTSQ16PA