Daikin FXSQ80P7VEB [308/370] Troubleshooting

Daikin FXSQ125PVE [308/370] Troubleshooting
Troubleshooting by Indication on the Remote Controller SiBE311209
299 Service Diagnosis
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Continued to A
(on the following page)
YES
NO
Check the indoor unit for
which “
UE
” is displayed. Is
the transmission error “
UE
caused on all indoor units?
YES
YES
YES
NO
NO
NO
YES
NO
NO
YES
Make sure there are no
hazardous situations, and
then turn ON the power
supply.
Is the power supply of the
indoor unit on which the “
UE
occurred, turned ON?
Has the setting of
centralized control group
No. been made with the
indoor unit on which the
UE
” occurred?
Was the
centralized control
group No. for
indoor unit
changed?
Can the setting of
centralized control group
No be made?
For VRV systems, can the setting
of centralized control group No.
be made in one and the same
refrigerant system?
Make correct setting of the
centralized control group No.
Check outdoor units to which
the refrigerant system is
connected.
Check whether or not there
are no problems with the
transmission wiring length,
types of cables and wires,
number of units connected,
and others. If no problems,
replace the indoor unit PCB.
Reset the power supplies of
every centralized control
equipment.
For the intelligent Touch
Controller, register the air
conditioner again while in
DIII-NET test operation
menu.