SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 258
Troubleshooting
Note: 1: Voltage measurement point
Refer to P.315.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are the characteristics of the
high pressure sensor normal?
(Make a comparison between
the voltage characteristics (1)
and the gauge pressure.)
NO
Replace the high pressure sensor.
Confirm which high pressure
sensor is abnormal using
outdoor unit "monitor mode".
1. Set the high pressure gauge
upright.
2. Connect the checker for
VRV to the gauge.
If the PCB pressure
detection normal? (Make a
comparison between the
checker pressure data and
the voltage characteristics
(1).)
Reset the operation, and then
restart the outdoor unit.
Are the
characteristics of
the high pressure
sensor normal?
Replace the outdoor unit main
PCB.
Replace the high pressure sensor.
Replace the outdoor unit main
PCB.
NO
NO
YES
YES
YES
Outdoor unit PCB (A1P)
+5V
GND
Micro-computer
A/D input
Measure DC voltage here.
CHECK 12
X32A
(4)
(3)
(2)
(1)
Red
Black
White
High pressure sensor
CHECK 12