Daikin FXSQ80P7VEB [238/370] Room temperature thermistor in remote controller abnormality

Daikin FXSQ40PVE [238/370] Room temperature thermistor in remote controller abnormality
Troubleshooting by Indication on the Remote Controller SiBE311209
229 Service Diagnosis
4.13 Room Temperature Thermistor in Remote Controller
Abnormality
Remote
Controller
Display
CJ
Applicable
Models
All indoor unit models
Method of Error
Detection
Error detection is carried out by temperature detected by room temperature thermistor in remote
controller. (1)
Error Decision
Conditions
When the room temperature thermistor in remote controller becomes disconnected or shorted
while the unit is running
Supposed
Causes
Defective room temperature thermistor in remote controller
Defective remote controller PCB
Troubleshooting
Note: 1: How to delete “the record of error codes”.
Press the “ON/OFF” button for 4 seconds and more while the error code is displayed in the
inspection mode.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
Replace the remote
controller.
YES
External factor other than
error.
(for example, noise etc.)
Clear the error code history.
(While in inspection mode,
press and hold the “ON/OFF”
button for a period of 4
seconds or more.)
Is "
CJ
" displayed
on the remote
controller?