SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 276
4.44 Refrigerant Shortage Alert
Remote
Controller
Display
U0
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Method of Error
Detection
Detect refrigerant shortage based on the temperature difference between low pressure or
suction pipe and heat exchanger.
Error Decision
Conditions
[In cooling mode]
Low pressure becomes 0.1MPa or less.
[In heating mode]
The superheated degree of suction gas becomes 20°C or more.
SH = Ts –Te
Ts: Suction pipe temperature detected by thermistor
Te: Saturated temperature corresponding to low pressure
Error is not determined. The unit continues the operation.
Supposed
Causes
Refrigerant shortage or refrigerant clogging (piping error)
Defective thermistor (R4T, R8T)
Defective low pressure sensor
Defective outdoor unit PCB (A1P)