Daikin FXSQ80P7VEB [263/370] Liquid pipe thermistor 1 r6t or r9t abnormality

Daikin FXSQ25PVE4 [263/370] Liquid pipe thermistor 1 r6t or r9t abnormality
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 254
4.30 Liquid Pipe Thermistor 1 (R6T or R9T) Abnormality
Remote
Controller
Display
J7
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Function Unit: BTSQ20PY1
Method of Error
Detection
Error is detected according to the temperature detected by liquid pipe thermistor.
Error Decision
Conditions
When the liquid pipe thermistor is short circuited or open circuited
Supposed
Causes
Defective connection of thermistor
Defective liquid pipe thermistor 1 (R6T or R9T)
Defective outdoor unit PCB
Troubleshooting
Refer to P.314.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the connector for
liquid pipe thermistor
connected to correct
outdoor unit PCB?
NO
YES
Is the
resistance measured after
removing the thermistor (R6T
or R9T) from outdoor unit
PCB normal?
CHECK 11
NO
YES
Connect the connector and operate
unit again.
Replace the thermistor (R6T or
R9T).
Replace the outdoor unit PCB
(A1P).
CHECK 11