Daikin FXSQ80P7VEB [135/370] List of swing flap operations

Daikin FXZQ50M9V1B [135/370] List of swing flap operations
SiBE311209 Outline of Control (Indoor Unit)
Function 126
9.6 List of Swing Flap Operations
Swing flaps operate as shown in table below.
1. L or LL only on FXFQ models
Fan
Flap
FXFQ
FXCQ
FXHQ
FXKQ
FXAQ
Heating
Hot start from defrosting
operation
Swing OFF Horizontal Horizontal Horizontal
Airflow direction set
OFF Horizontal Horizontal Horizontal
Defrosting operation
Swing OFF Horizontal Horizontal Horizontal
Airflow direction set
OFF Horizontal Horizontal Horizontal
Thermostat OFF
Swing LL Horizontal Horizontal Horizontal
Airflow direction set
LL Horizontal Horizontal Horizontal
Hot start from thermostat
OFF mode (for prevention
of cold air)
Swing LL Horizontal Horizontal Horizontal
Airflow direction set
LL Horizontal Horizontal Horizontal
Stop
Swing OFF Horizontal Horizontal Totally closed
Airflow direction set
OFF Horizontal Horizontal Totally closed
Cooling
Thermostat ON in dry
operation using micro
computer
Swing L
1
Swing Swing Swing
Airflow direction set
L
1
Set
Set Set
Thermostat OFF in dry
operation using micro
computer
Swing
OFF or L
Swing Swing Swing
Airflow direction set
Horizontal or Set
Set Set
Thermostat OFF in
cooling
Swing Set Swing Swing Swing
Airflow direction set
Set Set Set Set
Stop
Swing OFF Horizontal Horizontal Totally closed
Airflow direction set
OFF Horizontal Horizontal Totally closed
Micro computer control
(including cooling
operation)
Swing L Swing Swing Swing
Airflow direction set
LSetSetSet