Daikin REYQ96MTJU [135/273] The system operates for malfunction codes indicated in black squares however be sure to check and repair

Daikin REYQ96MTJU [135/273] The system operates for malfunction codes indicated in black squares however be sure to check and repair
Troubleshooting by Remote Controller SiUS39-602
124 Troubleshooting
Outdoor
Unit
LA 999Malfunction of power unit
LC 999Malfunction of transmission between inverter and
control PC board
169
P1 999Inverter over-ripple protection 171
P4 999
Malfunction of inverter radiating fin temperature rise sensor
172
PJ 999Faulty field setting after replacing main PC board or
faulty combination of PC board
173
System U0 879Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
174
U1 999Reverse phase / open phase 175
U2 999Power supply insufficient or instantaneous failure 176
U3 999Check operation is not conducted. 178
U4 999Malfunction of transmission between indoor and
outdoor units
179
U5 999Malfunction of transmission between remote
controller and indoor unit
181
U5 787Failure of remote controller PC board or setting
during control by remote controller
181
U7 999Malfunction of transmission between outdoor units 182
U8 997Malfunction of transmission between main and sub
remote controllers (malfunction of sub remote
controller)
184
U9 999Malfunction of transmission between indoor unit and
outdoor unit in the same system
185
UA 999Excessive number of indoor units etc. 187
UC 888Address duplication of central remote controller 188
UE 999Malfunction of transmission between central remote
controller and indoor unit
189
199
UF 999Refrigerant system not set, incompatible wiring /
piping
191
UH 999Malfunction of system, refrigerant system address
undefined
192
Central
Remote
Controller
and
Schedule
Timer
M1 8 or 79 9Central remote controller or schedule timer PC board
defect
194
201
M8 8 or 79 9Malfunction of transmission between optional
controllers for centralized control
195
202
MA 8 or 79 9Improper combination of optional controllers for
centralized control
196
203
MC 8 or 79 9Address duplication, improper setting 198
205
Heat
Reclaim
Ventilati
on
64 879Indoor unit’s air thermistor error
65 879Outside air thermistor error
6A 879Damper system alarm
6A 999Damper system + thermistor error
6F 879Malfunction of simple remote controller
6H 879Malfunction of door switch or connector
94 999Internal transmission error
Malfunction
code
Operation
lamp
Inspection
display
Unit No. Malfunction contents Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.