164 Test Operation
[Remote controller displays malfunction code]
REYQ8~16PY1
REYQ18~48PY1
Note:
If any malfunction codes other than the above are displayed, check the service manual for how
to respond.
Malfunction code Installation error Remedial action
E3, E4
F3, F6
UF
The shutoff valve of the outdoor unit is
left closed.
Open the shutoff valve.
U1
The phases of the power to the outdoor
unit is reversed.
Exchange two of the three phases (L1,
L2, L3) to make a proper connection.
U1
U4
LC
No power is supplied to an outdoor, BS
or indoor unit (including phase
interruption).
Make sure the power source wire is
properly connected to the outdoor, BS or
indoor unit and revise if necessary.
UF
There is conflict on the connection of
transmission wiring in the system.
Check if the refrigerant piping line and the
transmission wiring are consistent with
each other.
E3
F6
UF
Refrigerant overcharge.
Recalculate the additional amount
refrigerant from the piping length and
correct the refrigerant charge level by
recovering any excessive refrigerant with
a refrigerant recovery machine.
E4
F3
Insufficient refrigerant.
Check if the additional refrigerant
charge has been finished correctly.
Recalculate the additional amount
refrigerant from the piping length and
add the adequate amount.
U7, U4
UF, UH
Field wiring is connected to “TO MULTI
UNIT (Q1,Q2)” terminal on the outdoor
unit PC-board (A1P) when the system
is one outdoor system.
Remove the line from the “TO MULTI
UNIT (Q1, Q2)” terminal.
UA
The internal transmission wiring to “TO
MULTI UNIT (Q1,Q2)” for the single
outdoor unit system are disconnected.
Connect the internal transmission wiring
to “TO MULTI UNIT (Q1,Q2)”. (See the
wiring diagram.)
Malfunction code Installation error Remedial action
E3, E4, F3, F6
UF
The shutoff valve of the outdoor unit is
left closed.
Open the shutoff valve.
U1
The phases of the power to the outdoor
unit is reversed.
Exchange two of the three phases (L1,
L2, L3) to make a proper connection.
U1, U4, LC
No power is supplied to an outdoor, BS
or indoor unit (including phase
interruption).
Make sure the power source wire is
properly connected to the outdoor, BS or
indoor unit and revise if necessary.
UF
There is conflict on the connection of
transmission wiring in the system.
Check if the refrigerant piping line and the
transmission wiring are consistent with
each other.
E3, F6, UF Refrigerant overcharge.
Recalculate the additional amount
refrigerant from the piping length and
correct the refrigerant charge level by
recovering any excessive refrigerant with
a refrigerant recovery machine.
E4, F3 Insufficient refrigerant.
Check if the additional refrigerant
charge has been finished correctly.
Recalculate the additional amount
refrigerant from the piping length and
add the adequate amount.
U7, U4, UF, UH
Field wiring is connected to "TO MULTI
UNIT (Q1,Q2)" terminal on the outdoor
unit PC-board (A1P) when the system
is one outdoor system.
Remove the line from the “TO MULTI
UNIT (Q1, Q2)” terminal.