Field Setting Si37-701
178 Test Operation
(14) Setting of Air Flow Direction Adjustment Range
Make the following air flow direction setting according to the respective purpose.
Setting Table
Some indoor unit models are not equipped with draft prevention (upward) function.
(15) Setting of the static pressure selection (for FXDQ model)
(16) Humidification When Heating Thermostat is OFF
Setting to "Humidification Setting" turns ON the humidifier if suction temperature is 20ºC or
above and turns OFF the humidifier if suction temperature is 18ºC or below when the heating
thermostat is OFF.
(17) Setting of Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. The indoor fan carries
out residual operation for one minute after the thermostat is stopped. (For the purpose of
preventing dust on the air filter from falling off.)
Mode No. First Code No. Second Code No. Setting
13 (23) 4
01
Upward (Draft
prevention)
02 Standard
03
Downward (Ceiling
soiling prevention)
Model No. First Code No. Second Code No. External static pressure
13 (23) 5
01 Standard (15Pa)
02
High static pressure (44Pa)
Mode No. First Code No. Second Code No. Setting
15 (25) 1
01
02 Setting of humidifier
Mode No. First Code No. Second Code No. Contents
15 (25) 2
01
Without direct duct
connection
02
With direct duct
connection equipped
with fan