Daikin REYQ14PY1 [269/438] E9 outdoor unit malfunction of moving part of electronic expansion valve y1e y5e

Daikin REYQ14PY1 [269/438] E9 outdoor unit malfunction of moving part of electronic expansion valve y1e y5e
Troubleshooting by Indication on the Remote Controller Si37-701
258 Troubleshooting
3.19
E9
Outdoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y1E~Y5E)
Remote
Controller
Display
E9
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Check disconnection of connector
To be detected based on continuity existence of coil of electronic expansion valve
Malfunction
Decision
Conditions
No current is detected in the common (COM [+]) when power supply is ON.
Supposed
Causes
Disconnection of connectors for electronic expansion valve (Y1E)
Defect of moving part of electronic expansion valve
Defect of outdoor unit main PC board (A1P)