Daikin REYQ14PY1 [315/438] U4 malfunction of transmission between indoor units

Daikin REYQ14PY1 [315/438] U4 malfunction of transmission between indoor units
Troubleshooting by Indication on the Remote Controller Si37-701
304 Troubleshooting
3.48
U4
Malfunction of Transmission between Indoor Units
Remote
Controller
Display
U4
Applicable
Models
All model of indoor unit
REYQ8P~48P
Method of
Malfunction
Detection
Check if the transmission between indoor unit and outdoor unit is correctly executed using
microcomputer.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
or wrong wiring
Outdoor unit power supply is OFF
System address doesn’t match
Defect of indoor unit PC board
Defect of outdoor unit PC board