Daikin REYQ14PY1 [319/438] U7 outdoor unit transmission failure across outdoor units

Daikin REYQ20PY1 [319/438] U7 outdoor unit transmission failure across outdoor units
Troubleshooting by Indication on the Remote Controller Si37-701
308 Troubleshooting
3.50
U7
Outdoor Unit: Transmission Failure (Across Outdoor
Units)
Remote
Controller
Display
U7
Applicable
Models
All models of outdoor units
Method of
Malfunction
Detection
Microcomputer checks if transmission between outdoor units.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Connection error in connecting wires between outdoor unit and outdoor unit outside control
adapter
Connection error in connecting wires across outdoor units
Setting error in switching cooling/ heating
Integrated address setting error for cooling/ heating
(function unit, outdoor unit outside control adapter)
Defective outdoor unit PC board (A1P or A3P)
Defective outdoor unit outside control adapter