Fan coils without tank Application examples with several heat emitters
Using different heat emitters means using different water set points
for the system.
Such installations must be done using a balancing bottle and each
kind of heat emitter should have a specic pump.
Refer to chapter "9.8. Multiple set point control" on page 46 for more
information about the conguration of your system.
1 Outdoor unit 11 Electronic expansion valve
2 Indoor unit 12 Indoor unit refrigerant stop
valve
3 Refrigerant heat exchanger
4 Water heat exchanger C1 Remote controller
5 Compressor A Installation place
6 Pump B Living room
7 Shut-off valve M1...M3 Individual motorized valve
to control loop fan coils
(eld supply)
8 Collector (eld supply)
9 By-pass valve (eld supply
10 FCU: Fan coil unit (eld
supply)
T1...T3 Individual room thermostat
(eld supply)
7 8432 916
10
512
T3
A B
C1
M3
M2
M1
11
1112
FCU3
10
T2
FCU2
10
T1
FCU1
1 Outdoor unit 13 Shut-off valve (eld supply)
2 Indoor unit 14 By-pass valve (eld supply)
3 Electronic expansion valve 15 FCU: Fan coil unit (eld
supply)
4 Refrigerant heat exchanger 16 Shut-off valve (eld supply)
5 Water heat exchanger 17 Radiator (eld supply)
6 Pump 18 Mixing valve (eld supply)
7 Motorized 3-way valve
(optional)
19 Pump (eld supply)
8 Domestic hot water tank
(optional)
20 Non-return valve (eld
supply)
9 Compressor C1 Remote controller
10 Shut-off valve TRD1 Temperature reducing
device 1 (eld supply)
11 Balancing bottle (eld supply)
12 FHL: Floor heating loop (eld
supply)
TRD2 Temperature reducing
device 2 (eld supply)
3 34 5 6 8221
21
1
17
1919
18
20 20
19
18
11
M
35°C
FHL
45°C
65°C
FCU
1512 14 141613
9
10 10
7
C1
TRD1 TRD2