Installation manual
34
EKHVMRD50+80ABV1 + EKHVMYD50+80ABV1
Daikin Altherma indoor unit
4P404420-1 2015.04
11 Air purge valve
Make sure the air purge valve of the heat pump is open (at least
2 turns).
Make sure the air purge valve of the heater kit is open (at least
2 turns). See installation manual of the heater kit.
12 Shut-off valves
Make sure that the shut-off valves are correctly installed and
fully open.
Once all checks are fullled, the unit must be closed, only then can
the unit be powered up. When the power supply to the indoor unit is
turned on, "88" is displayed on the remote controller during its
initialization, which might take up to 30 seconds. During this process
the remote controller can not be operated.
9.2. Final air purging
To get rid of all the air in the system, the pump should be operated.
Therefore, change the eld setting [E-04] as explained in the chapter
"9.3. Field settings" on page 34. More details about setting "[E-04]
Pump only operation" can be found on page 41.
In case of an optional tank installed with the EKHVMYD units the
system includes two 3-way valves (cool/heat and heat/domestic hot
water). If no tank is installed, only 1 3-way valve is included.
In case of an optional tank installed with the EKHVMRD units the
system includes one 3-way valves (heat/domestic hot water).
9.3. Field settings
The indoor unit should be congured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user demand. Therefore, a number of so called eld settings are
available. These eld settings are accessible and programmable
through the user interface on the indoor unit.
Each eld setting is assigned a 3-digit number or code, for example
[5-03], which is indicated on the user interface display. The rst digit
[5] indicates the 'rst code' or eld setting group. The second and
third digit [03] together indicate the 'second code'.
A list of all eld settings and default values is given in the "9.9. Field
setting table" on page 49. In this list we provided for 2 columns to
register the date and value of altered eld settings at variance with
the default value.
A detailed description of each eld setting is given under
"9.5. Detailed description" on page 35.
9.4. Procedure
To change one or more eld settings, proceed as follows.
1 Press the button for a minimum of 5 seconds to enter FIELD
SET MODE.
The icon (3) will be displayed. The current selected eld
setting code is indicated (2), with the set value displayed to
the right (1).
2 Press the button to select the appropriate eld setting
rst code.
3 Press the button to select the appropriate eld setting
second code.
4 Press the button and button to change
the set value of the select eld setting.
5 Save the new value by pressing the button.
6 Repeat step 2 through 4 to change other eld settings as
required.
7 When nished, press the button to exit FIELD SET MODE
.
Operating the system with closed valves will damage the
pump!
NOTE
Changes made to a specic eld setting are only
stored when the button is pressed.
Navigating to a new eld setting code or pressing
the button will discard the change made.
The eld settings are grouped by their eld setting
rst code.
For example, eld settings [0-00]; [0-01]; [0-02];
[0-03] are dened as "Group 0".
When different values are changed within the
same group, pressing the button will save all
the values changed within this group.
Be aware of this when changing eld settings
within the same group and pressing on the
button.
NOTE
Before shipping, the set values have been set as
shown under "9.9. Field setting table" on page 49.
When exiting FIELD SET MODE, "88" may be
displayed on the remote controller LCD while the
unit initializes itself.
NOTE
When running through the eld settings you may notice
that there are some more eld settings as there are
mentioned in the "9.9. Field setting table" on page 49.
These eld settings are not applicable and may not
be changed!
2
3
1