Daikin EKHVMYD50ABV1 [28/64] Setting the pre pressure of the expansion vessel

Daikin EKHVMYD50ABV1 [28/64] Setting the pre pressure of the expansion vessel
Installation manual
26
EKHVMRD50+80ABV1 + EKHVMYD50+80ABV1
Daikin Altherma indoor unit
4P404420-1 2015.04
How to check if the pre-pressure of the system needs to be changed:
Step 1: dene the needed leaving water temperature in the
system: e.g. 65°C
Step 2: dene the maximal water volume in the system with the
default pre-pressure of 1 bar
If the total water volume of the system is <150 l:
no change of pre-pressure needed.
If the total water volume of the system is >150 l:
change of pre-pressure needed.
Setting the pre-pressure of the expansion vessel
When it is required to change the default pre-pressure of the
expansion vessel (1 bar), keep in mind the following guidelines:
Use only dry nitrogen to set the expansion vessel pre-pressure.
Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system. Therefore, the pre-pressure
should only be adjusted by a licensed installer.
Accessing the expansion vessel from the front:
Remove the front decoration panel.
Remove the switch box.
Remove the small expansion vessel (2 l) only in case of
EKHVMYD.
65°C water temperature
A Pre-pressure (bar)
B System water volume (l)
NOTE
Never change the pre-pressure of the system to a
value lower than 0.3 bar.
In this example (when the needed water temperature is
65°C) the maximal water volume is 215 l.
2.50
2.00
1.50
1.00
0.50
0.00
20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 27
0
B
A
NOTE
To set the pre-pressure, the expansion vessel needs to
be accessed from the front or the right.
1 Front decoration panel
2 Switch box
3 Small expansion vessel (2 l)
4 Sound panel
5 Right decoration panel
6 Pre-charge valve
1 2 3 4 5
6

Содержание

Скачать