Daikin EKHVMYD50ABV1 [33/64] Installation and connection of the remote controller

Daikin EKHVMYD50ABV1 [33/64] Installation and connection of the remote controller
EKHVMRD50+80ABV1 + EKHVMYD50+80ABV1
Daikin Altherma indoor unit
4P404420-1 2015.04
Installation manual
31
Installation and connection of the remote controller
The unit is equipped with a remote controller offering user-friendly
way to set up, use and maintain the unit. Before operating the remote
controller, follow this installation procedure.
1 Remove the front part of the remote controller.
Insert a slotted screwdriver into the slots (1)
in the rear part of the remote controller, and
remove the front part of the remote
controller.
2 Fasten the remote controller on a at
surface.
3 Wire the unit.
Connect the terminals on top of the front part of the remote
controller and the terminals inside the unit (P1 to X3M: P1, P2 to
X3M: P2).
4 Reattach the upper part of the remote controller.
First begin tting from the clips at the
bottom.
NOTE
The wiring for connection is not included.
The remote controller, delivered in a kit, has to be
mounted indoors.
When the remote controller thermostat function is
used, select the installation location considering it
should be a place:
where the average temperature in the room can be
detected,
that is not exposed to direct sunlight,
that is not near a heat source,
that is not affected by outside air or air draught due
to e.g. door opening/closing,
where the display is kept clean,
where the temperature is between 0°C and 50°C,
where the relative humidity is maximum 80%.
NOTE
Be careful not to distort the shape of the lower
part of the remote controller by over tightening the
mounting screws.
NOTE
If next to the standard remote controller the
optional remote controller is installed as well:
Connect the electrical wires of both remote
controllers in the same way like described
below.
Select a master and a slave remote controller
by switching the SS1 selector switch.
Only the remote controller set as master can
work as room thermostat.
1
SS
M
PCB
SS1
S Slave
M Master
1 Unit
2 Rear part of the remote controller
3 Front part of the remote controller
4 Wired from the rear
5 Wired from the top
6 Notch the part for the wiring to pass through with nippers,
etc.
NOTE
Peel the shield for the part that
has to pass through the inside of
the remote controller case ( l ).
Be careful not to pinch the wiring when attaching.
P1P2
6
2
1
3
4 5
P1P2
P2
P1
P2
P1
X3M
X3M
1