Installation manual
54
EKHVMRD50+80ABV1 + EKHVMYD50+80ABV1
Daikin Altherma indoor unit
4P404420-1 2015.04
11.3. Vacuuming/recovery and maintenance on refrigerant side
This ow chart indicates the main items and actions which have to be considered during vacuuming/recovery operations on the system. When
certain settings and operations explained in the ow chart are not followed this can be improper operation of the unit due to bad vacuuming/
recovery. In case of problems, please contact your local dealer.
R134a circuit needs
to be maintenanced?
Yes Indoor unit remocon
setting [E-00]=1 to
open electronic
expansion valve
Start recovery/
vacuuming of
R134a circuit
No
R410A circuit needs
to be maintenanced?
Ye s
First installation
No
Maintenance
Ye s Ye s
Indoor unit was
powered on?
No
Other indoor or
outdoor unit(s) were
powered on?
No Open stop valve
indoor units
(2)
(a)
. Field
piping and
indoor unit
R410A
vacuuming can
start
Complete indoor
system R410A
circuit?
No
1 indoor unit?
Close this indoor
unit stop valve
(2)
(a)
Ye s Ye s Ye s
Valves on R410A
circuit need to be
opened. Apply
outdoor unit eld
setting 2-21 (see
installation manual of
outdoor unit)
Ye s
Field piping +
indoor + outdoor
unit(s)?
Apply outdoor
unit eld setting
2-21 (see
installation
manual of
outdoor unit)
No
Open all
stopvalves (1)
and (2)
(a)
Field piping only +
indoor unit
Recovery start +
measure
recovered
R410A amount
Open stop valve
(2)
(a)
indoor units.
Field piping and
indoor unit R410A
vacuuming can start
(a) (1) and (2) refers to the legend of the gure in next chapter "System overview" on page 55.
Apply outdoor
unit eld setting
2-21 (see
installation
manual of
outdoor unit)
Close stop valve
outdoor unit (1)
(a)
Maintenance
Open stop valve
indoor unit (2)
(a)
Start vacuuming
Apply outdoor unit
eld setting 2-21
(see installation
manual of outdoor
unit)
Recharge
system with
measured
R410A amount
Cancel outdoor
unit eld setting
2-21 (see
installation
manual of
outdoor unit)
Open stop
valve(s) (if
applicable)
Restart system