Daikin EKHVMYD50ABV1 [59/64] Error codes

Daikin EKHVMYD50ABV1 [59/64] Error codes
EKHVMRD50+80ABV1 + EKHVMYD50+80ABV1
Daikin Altherma indoor unit
4P404420-1 2015.04
Installation manual
57
Symptom 6: Space heating capacity shortage at low outdoor
temperatures
12.5. Error codes
When a safety device is activated, the user interface LED will be
ashing, and an error code will be displayed.
A list of errors and corrective actions can be found in the table below.
Reset the safety by pushing the button.
In case this procedure for resetting the safety is not successful,
contact your local dealer.
For other error codes which may be displayed during the system test
run or operation, see the installation manual of the outdoor unit.
POSSIBLE CAUSES CORRECTIVE ACTION
The heater kit is not activated. Check that the "heater kit operation
status" eld setting [6-02] is turned
on, see "Field settings" in the
operation manual of the indoor unit.
Error
code
Failure cause Corrective action
A1 Failure of writing memory
(EEPROM error)
Contact your local dealer.
A6 Malfunction of pump in water
circuit (M1P+M2P)
Make sure waterow is
possible (open all valves in the
circuit).
Force clean water through the
unit.
A9 R410A expansion valve error
(K1E)
Check wiring connections.
Contact your local dealer.
AA Heater kit thermal cut out error (if
the heater kit option installed)
Make sure the circuit is lled
with water (no air inside).
Make sure waterow is
possible (open all valves in the
circuit).
Heater kit connected to the
benet kWh rate power supply
Make sure the heater kit is
connected to a normal power
supply.
AE Water system warning low ow is
expected by the unit.
Check lter.
Make sure all valves are open.
AJ Capacity error Contact your local dealer.
C1 Bad ACS communication Contact your local dealer.
C4 R410A liquid thermistor error
(R3T)
Check wiring connections.
Contact your local dealer.
C5 Domestic hot water tank
thermistor error (R2T)
Check wiring connections.
Check if the domestic hot
water option is turned active
(refer to eld setting [6-00]).
Contact your local dealer.
C9 Returning water thermistor error
(R4T)
Check wiring connections.
Contact your local dealer.
CA Heating leaving water thermistor
error (R5T)
Check wiring connections.
Contact your local dealer.
CE Cooling leaving water thermistor
error (R9T)
Check wiring connections.
Contact your local dealer.
CJ Remote controller thermostat
thermistor error
Contact your local dealer.
E1 Compressor PCB error Contact your local dealer.
E3 High pressure error (S1PH) Check wiring connections on
outdoor unit and indoor unit.
Make sure the circuit is lled
with water (no air inside, e.g.
is the air purge open?)
Make sure the domestic hot
water tank is lled with water.
Make sure water ow is
possible (open all valves in the
circuit).
Make sure the water lter is
not blocked.
Make sure all refrigerant stop
valves are open.
Contact your local dealer.
E3 Thermal cut-out error (Q2L) Reset the thermal cut-out.
Contact your local dealer.
E4 Low pressure error (B1PL) Check wiring connections on
outdoor unit and indoor unit.
Contact your local dealer.
E5 Overload activation of
compressor (M1C)
Contact your local dealer.
E9 R134a expansion valve error
(K2E) or R410A expansion valve
error (K3E)
Check wiring connections.
Contact your local dealer.
F3 Discharge temperature error Contact your local dealer.
J3 Discharge thermistor error (R6T) Check wiring connections.
Contact your local dealer.
J5 R134a liquid thermistor error Check wiring connections.
Contact your local dealer.
J6 R410A liquid thermistor error
(R10T)
Check wiring connections.
Contact your local dealer.
J7 R410A suction thermistor error
(R11T)
Check wiring connections.
Contact your local dealer.
JA R134a high pressure sensor
error (B1PH)
Check wiring connections.
Contact your local dealer.
JC R134a low pressure sensor error
(B1PL)
Check wiring connections.
Contact your local dealer.
L1 Compressor inverter PCB error Contact your local dealer.
L4 Fin thermistor error Check wiring connections.
Contact your local dealer.
L5 Compressor inverter PCB error Contact your local dealer.
L8 Compressor inverter PCB error Contact your local dealer.
L9 Compressor inverter PCB error Contact your local dealer.
LC Inverter communication problem Contact your local dealer.
LH Converter error Contact your local dealer.
P1 Main compressor PCB error Contact your local dealer.
PJ Bad combination inverter
components
Contact your local dealer.
U2 Power supply error Check wiring connections.
Contact your local dealer.
U4 QA transmission problem Contact your local dealer.
U5 Remote controller error Contact your local dealer.
UA Type connection problem Wait till initialisation between
outdoor unit and indoor unit is
nished (after power ON, wait
at least 12 minutes).
Contact your local dealer.
UC Address duplication error Contact your local dealer.
UF Transmission problem with
outdoor unit
Contact your local dealer.
UF QA wiring problem Contact your local dealer.
UH Address error Contact your local dealer.
Error
code
Failure cause Corrective action