9.9. Field setting table
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value
0 Remote control setup
00 User permission level
2 2~3 1
01 Room temperature compensation value
0 5~5 0.5 °C
02 Not applicable. Do not change the default value.
1 ——
03 Status: space heating schedule timer mode
Method 1=1 / Method 2=0
1 (ON) 0/1 ——
04 Status: space cooling schedule timer mode
Method 1=1 / Method 2=0
1 (ON) 0/1 ——
1 Automatic storage timing for domestic water heating
00 Status: night time storage
1 (ON) 0/1 ——
01 Night time storage start time
1:00 0:00~23:00 1:00 hour
02 Status: day time storage
0 (OFF) 0/1 ——
03 Day time storage start time
15:00 0:00~23:00 1:00 hour
2 Automatic setback function
00 Status: setback operation
1 (ON) 0/1 ——
01 Setback operation start time
23:00 0:00~23:00 1:00 hour
02 Setback operation stop time
5:00 0:00~23:00 1:00 hour
3 Weather dependent set point
00 Low ambient temperature (Lo_A)
10 20~5 1 °C
01 High ambient temperature (Hi_A)
15 10~20 1 °C
02 Set point at low ambient temperature (Lo_Ti)
70 25~80 1 °C
03 Set point at high ambient temperature (Hi_Ti)
45 25~80 1 °C
4 Disinfection function
00 Status: disinfection operation
1 (ON) 0/1 ——
01 Disinfection operation day selection
Fri Mon~Sun ——
02 Disinfection operation start time
23:00 0:00~23:00 1:00 hour
5 Automatic setback and disinfection set point
00 Set point: disinfection operation temperature
70 60~75 5 °C
01 Disinfection operation time duration
10 5~60 5 min
02 Leaving water setback temperature
5 0~10 1 °C
03 Room setback temperature
18 17~23 1 °C
04 Not applicable. Do not change the default value.
0 ——
6 Option setup
00 Domestic hot water tank installed
0 (OFF) 0/1 ——
01 Optional room thermostat installed
0 (OFF) 0/1 ——
02 Optional backup heater installed
0 (OFF) 0/1 ——
03 Optional solar kit installed
0 (OFF) 0/1 ——
04 Benet kWh power supply mode
0 0/2 1
7 Option setup
00 Not applicable. Do not change the default value.
0 ——
01 Not applicable. Do not change the default value.
0 ——
02 Multiple set point pattern
0 (A) 0/1 ——
03 Multiple set point 1
0 (OFF) 0/1 ——
04 Multiple set point 2
0 (OFF) 0/1 ——
8 Option setup
00 Remote controller temperature control
1 (ON) 0/1 ——
01 Backup heater kit optional setting
1 (ON) 0/1 ——
02 Emergency mode
0 (OFF) 0/1 ——
03 Status: low noise level
1 1~3 1
04 Status: freeze-up prevention
0 0~2 1