Daikin EKHVMYD50ABV1 [30/64] Internal wiring parts table

Daikin EKHVMYD50ABV1 [30/64] Internal wiring parts table
Installation manual
28
EKHVMRD50+80ABV1 + EKHVMYD50+80ABV1
Daikin Altherma indoor unit
4P404420-1 2015.04
Point of attention regarding quality of the public electric power
supply.
This equipment complies with respectively:
EN/IEC 61000-3-11
(1)
provided that the system impedance Z
sys
is less then or equal to Z
max
.
EN/IEC 61000-3-12
(2)
provided that the short-circuit power S
sc
is greater than or equal to the minimum S
sc
value
at the interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the equipment
to ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with
respectively:
Z
sys
less than or equal to Z
max
S
sc
greater than or equal to the minimum S
sc
value.
8.2. Internal wiring – Parts table
Refer to the wiring diagram sticker on the unit. The abbreviations
used are listed below:
A1P............................ Main PCB
A2P............................ User interface PCB
A3P............................ Control PCB
A4P............................ Inverter PCB
A5P............................ QA PCB
A6P............................ Filter PCB
A7P......................*.... Digital I/O PCB
A8P......................*.... Demand PCB
A9P............................ Multi tenant PCB
A10P....................*.... Thermostat PCB
A11P....................*.... Receiver PCB
A12P....................*.... Solar pump station PCB (EKSRPS3)
B1PH ......................... High pressure sensor
B1PL.......................... Low pressure sensor
BSK .....................*.... Solar pump station relay (EKSRPS3)
C1~C3 ....................... Filter capacitor
C1~C3 (A4P)............. PCB capacitor
DS1 (A*P).................. Dip switch
F1U............................ Fuse (T, 3.2 A, 250 V)
F1U (A1P,A3P,A9P) ... Fuse (T, 3.15 A, 250 V)
F1U (A6P) ................. Fuse (T, 6.3 A, 250 V)
F1U,F2U (A7P)....*.... Fuse (5 A, 250 V)
F3U,F4U..............*.... Fuse (T, 6.3 A, 250 V)
HAP (A*P) ................. PCB LED
IPM1 .......................... Integrated power module
K1A~K3A................... Interface relay
K1E~K3E................... Electronic expansion valve
K*R (A*P) .................. PCB relay
K1S~K3S................... 3-way valve
K4S..................... #.... 2-way valve
M1C........................... Compressor
M1F ........................... Switch box cooling fan
M1P,M2P ................... DC inverter pump
PC (A11P) ...........*.... Power circuit
PHC1...................*.... Optocoupler input circuit
PS (A*P) .................... Switching power supply
Q1DI,Q2DI.......... #.... Earth leakage protector
Q2L............................ Thermal protector water piping
R1,R2 (A4P) .............. Resistance
R1L............................ Reactor
R1H (A10P) .........*.... Humidity sensor
R1T (R10P) .........*.... Ambient sensor
R2T......................*.... Domestic hot water tank thermistor
R2T......................*.... External sensor (oor or ambient)
R3T............................ Liquid thermistor R410A
R4T............................ Returning water thermistor
R5T............................ Leaving water thermistor (heating)
R6T............................ Discharge thermistor
R7T............................ Liquid thermistor R134a
R8T............................ Fin thermistor
R9T............................ Leaving water thermistor (cooling)
ATTENTION
The equipment described in this manual may cause
electronic noise generated from radio-frequency energy.
The equipment complies to specications that are
designed to provide reasonable protection against such
interference. However, there is no guarantee that
interference will not occur in a particular installation.
It is therefore recommended to install the equipment and
electric wires keeping proper distances away from stereo
equipment, personal computers, etc....
In extreme circumstances you shall keep distances of 3m
or more and use conduit tubes for power and transmission
lines.
WARNING
This is a class A product. In a domestic environment this
product may cause radio interference in which case the
user may be required to take adequate measures.
(1) European/International Technical Standard setting the limits for voltage
changes, voltage uctuations and icker in public low-voltage supply
systems for equipment with rated current 75 A.
(2) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems
with input current >16 A and 75 A per phase.
Z
max
() Minimum S
sc
value
EKHVMYD50A 0.46 1459 kVA
EKHVMYD80A 0.46 1459 kVA
EKHVMRD50A 0.46 1459 kVA
EKHVMRD80A 0.46 1459 kVA