Daikin RMXS140E8V1B [90/393] Demand operation

Daikin CTXG50EV1BW [90/393] Demand operation
SiBE18-821 Other Control
Function 77
5. Other Control
5.1 Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting” or
external input by external control adaptor is required.
[Demand 1 setting]
5.2 Heating Operation Prohibition
Heating operation is prohibited above 24°CDB outdoor air temperature.
Setting Standard for upper limit of power consumption
Demand 1 setting 1 Approx. 60%
Demand 1 setting 2 (factory setting) Approx. 70%
Demand 1 setting 3 Approx. 80%