Omron NYB1E-C1006 [153/276] Dc power supply

Omron NYB1E-D13E6 [153/276] Dc power supply
Power Connector Wiring Materials
Use the power supply connector that was supplied to connect the power supply to the Industrial Box
PC.
Select power supply conductors with consideration to the voltage drop and heat generation for the
cable length at the installation environment.
Always use twisted wires to minimize the occurrence of electrical disturbance.
Recommended power supply conductor sizes are provided in the table.
Wire type Conductor cross-section
Solid conductor
0.5 to 10 mm
2
Flexible conductor
0.5 to 6 mm
2
Flexible conductor, with ferrule and no plastic sleeve
0.5 to 6 mm
2
Flexible conductor, with ferrule and plastic sleeve
0.5 to 4 mm
2
Minimum AWG according to UL/cUL 20
Maximum AWG according to UL/cUL 8
Power Supply Connector
DC Power Supply
The OMRON S8VK-series power supply is recommended for use with the Industrial Box PC.
Additional Information
Refer to 3-10-10 Power Supply on page 3-30 for more information.
Refer to
4-1-3 Power Consumption Specifications on page 4-4 for power consumption details.
5 Installation
5-37
NY-series Industrial Box PC Hardware User's Manual (W553)
5-4 Wire
5
5-4-3 Wire the Power Connector