Omron NYB1E-C1006 [171/276] Installation

Omron NYB1E-413M1 [171/276] Installation
10 Simulate a power interruption and confirm a correct shutdown of the Box PC.
Start the Box PC
Start applications
Create a power interruption
Monitor the shutdown sequence and confirm a correct shutdown sequence
The UPS is connected and configured.
The Box PC will shut down properly in case of a power supply interruption and restart automatically
when the power is restored.
Additional Information
The default Input sensitivity setting is Standard voltage sensitivity and this is correct.
Do not set this parameter to Low voltage sensitivity. Doing so can cause a system malfunc-
tion when switching to battery mode.
5 Installation
5-55
NY-series Industrial Box PC Hardware User's Manual (W553)
5-8 Connect UPS
5
5-8-2 Connect UPS Using the I/O Connector