Electrical Installation Tester
Making Measurements
17
Note
For normal insulation with high resistance, the actual test voltage (U
N
)
should always be equal to or higher than the programmed voltage. If
insulation resistance is bad, the test voltage is automatically reduced
to limit the test current to safe ranges.
Measuring Continuity
R
LO
apx003f.eps
Figure 9. Continuity Zero Display/Switch and Terminal Settings
A continuity test is used to verify the integrity of connections by making a high
resolution resistance measurement. This is especially important for checking
Protective Earth connections.
Note
In countries where electrical circuits are laid out in a ring, it is
recommended that you make an end-to-end check of the ring at the
electrical panel.
XW Warning
Measurements should only be performed on de-energized
circuits.
Measurements may be adversely affected by impedances or
parallel circuits or transient currents.
To measure continuity:
1. Turn the rotary switch to the R
LO
position.
2. Use the L and PE (red and green) terminals for this test.
3. Before making a continuity test, use the Zero adapter to zero the test
leads. Press and hold Z until the ZERO annunciator appears. The
tester measures probe resistance, stores the reading in memory, and