Fluke 1650B [39/62] Storing and recalling measurements model 1653b only

Fluke 1650B [39/62] Storing and recalling measurements model 1653b only
Electrical Installation Tester
Storing and Recalling Measurements
31
L1
L2
L3
PE (L2/Green)
L (L1/Red)
N (L3/Blue)
apx022f.eps
Figure 21. Phase Sequence Test Connection
To perform a phase sequence test:
1. Turn the rotary switch to the Q position.
2. The primary (upper) display shows:
123 for correct phase sequence.
321 for reversed phase sequence.
Dashes (---) instead of numbers if insufficient voltage is sensed.
Storing and Recalling Measurements
(Model 1653B Only)
Using Memory Mode
You can store up to 500 measurements on the tester. The information stored
for each measurement consists of the test function and all user selectable test
conditions.
Data for each measurement is assigned a data set number, data subset
number, and a data id number. Memory location fields are used as described
below.
Field Description
f Use the data set field (a) to indicate a location such as a
room or electrical panel number.
g Use the data subset field (b) for circuit number.
h The data id number field (c) is the measurement number.
The measurement number automatically increments. The
measurement number can also be set to a previously used
value to overwrite an existing measurement.