Fluke 1650B [60/62] Mains wiring test

Fluke 1650B [60/62] Mains wiring test
165XB
Users Manual
52
Mains Wiring Test
Icons (a, b, c) indicate if L-PE or L-N terminals are reversed.
Instrument operation is inhibited and an error code is generated if the input
voltage is not between 100 V and 500 V. The UK Loop and RCD tests are
inhibited if the L-PE or the L-N terminals are reversed.
Operating Ranges and Uncertainties per EN 61557
Function Display Range
EN 61557
Measurement
Range
Operating
Uncertainty
Nominal Values
Volts
EN 61557-1
0.0 V ac –
500 V ac
50 V ac –
500 V ac
± (2 % + 2 dgt)
U
N
= 230/400 V ac
f = 50/60 Hz
R
LO
EN 61557-4
0.00 Ω - 2000 Ω
0.2 Ω - 2000 Ω
± (10 % + 2 dgt)
4.0 V dc <U
Q
>24 V dc
R
LO
2.00 Ω I
N
200 mA
R
ISO
EN 61557-2
0.00 MΩ -
1000 MΩ
1 MΩ - 200 MΩ
± (10 % + 2 dgt)
200 MΩ -
1000 MΩ
± (15 % + 2 dgt)
U
N
=
50/100/250/500/1000
V dc
I
N
= 1.0 mA
Z
I
0.00 Ω - 2000 Ω
2 Ω - 1000 Ω
± (15 % + 2 dgt)
Z
I
EN 61557-3
R
E
0.00 Ω - 2000 Ω
10 Ω - 1000 Ω
± (10 % + 2 dgt)
U
N
= 230/400 V ac
f = 50/60 Hz
I
K
= 0 A – 10.0 kA
ΔT
0.0 ms –
2000 ms
25 ms –
2000 ms
± (10 % + 1 dgt)
ΔT =
10/30/100/300/500/1000
mA
ΔT, I
ΔN
EN 61557-6
I
ΔN
0.5 mA - 550 mA
0.5 mA –
550 mA
± (10 % + 1 dgt)
I
ΔN
= 10/30/100/300/500
mA
R
E
EN 61557-5
0.0 Ω - 2000 Ω
10 Ω - 2000 Ω
± (10 % + 2 dgt)
f = 128 Hz
Phase
EN 61557-7
1 : 2 : 3