Fluke 1650B [35/62] Warning

Fluke 1650B [35/62] Warning
Electrical Installation Tester
Making Measurements
27
Measuring RCD Tripping Current
(Models 1652B and 1653B Only)
apx009f.eps
Figure 16. RCD Tripping Current/Switch and Terminal Settings
This test measures the RCD tripping current by applying a test current and then
gradually increasing the current until the RCD trips. You can use the test leads
or mains cord for this test. A 3-wire connection is required.
XW Warning
Test the connection between the N-conductor and earth
before starting the test. A voltage between the N-conductor
and earth may influence the test.
Leakage currents in the circuit following the residual current
protection device may influence measurements.
The displayed fault voltage relates to the rated residual
current of the RCD.
Potential fields of other earthing installations may influence
the measurement.
Note
If the L and N terminals are reversed, the tester will auto-swap them
internally and continue testing. If the tester is configured for UK
operation, testing will halt
and you will need to determine why the L
and N are swapped
. This condition is indicated by arrows above or
below the terminal indicator symbol (b).Type A RCDs do not have
the 1000mA option available.
To measure RCD tripping current:
1. Turn the rotary switch to the I
ΔN
position.
2. Press 1 to select the RCD current rating (10, 30, 100, 300, or 500 mA).