Fluke 1650B [32/62] Warning

Fluke 1650B [32/62] Warning
165XB
Users Manual
24
special nominal current setting other than the standard options, you can use a
custom setting with the VAR mode.
Note
When measuring trip time for any type of RCD, the tester first does a
pretest to determine if the actual test will cause a fault voltage
exceeding the limit (25 or 50 V). To avoid having an inaccurate trip
time for S type (time delay) RCDs, a 30 second delay is activated
between the pretest and the actual test. This RCD type needs a delay
because it contains RC circuits that are required to settle before
applying the full test.
XW Warning
Test the connection between the N-conductor and earth
before starting the test. A voltage between the N-conductor
and earth may influence the test.
Leakage currents in the circuit following the residual current
protection device may influence measurements.
The displayed fault voltage relates to the rated residual
current of the RCD.
Potential fields of other earthing installations may influence
the measurement.
Equipment (motors, capacitors) connected downstream of
the RCD may cause considerable extension of the tripping
time.
Note
If the L and N terminals are reversed, the tester will auto-swap them
internally and continue testing. If the tester is configured for UK
operation, testing will halt
and you will need to determine why the L
and N are swapped
. This condition is indicated by arrows above or
below the terminal indicator symbol (b).Type A RCDs do not have
the 1000mA option available.
To measure RCD tripping time:
1. Turn the rotary switch to the ΔT position.
2. Press 1 to select the RCD current rating (10, 30, 100, 300, 500, or 1000
mA).
3. Press 2 to select a test current multiplier (x ½, x 1, x 5, or Auto). Normally
you will use x 1 for this test.
Note
Model 1651B does not allow the Auto Selection.